Check the cold and hot limits of a solar string
Start with the panel’s open-circuit voltage at standard test conditions and its Voc temperature coefficient in %/°C. With a negative coefficient, colder cells raise open-circuit voltage. Include a design reserve and check the hottest operating Vmp against the battery charge voltage and controller start requirement.
The 100 V, 150 V and 250 V rows are voltage-class screens. Check the exact Victron Energy or other manufacturer model for battery-voltage support, start and operating limits, PV short-circuit current and output rating. Use the lowest expected site cell temperature.
Formulas
Cold panel Voc = STC Voc × [1 + (coefficient %/°C ÷ 100) × (cold °C − 25 °C)] for temperatures below 25 °CCold string Voc = series panels × cold panel VocCold string Voc must be below controller ceiling × (1 − voltage reserve)
Worked example
At −15 °C, a 41 V panel rated −0.30%/°C reaches about 45.92 V. Three in series reach 137.76 V, above the 135 V design ceiling of the 150 V class with 10% reserve. With the 58.4 V battery charge setting, the 250 V voltage class returns a 3S × 2P candidate.