48V 5kW Inverter DC Cable & Fuse Size Calculator

Screen DC cable gauge, voltage drop and fuse candidates for a 5,000 W inverter on a 48 V class LiFePO4 battery.

Jump to results

Inputs

Circuit and voltage drop
Use full charge voltage when screening DC fuses.
Cable and installation
Enter the combined ambient and bundling adjustment.

Results

Estimates
Minimum reference gauge1/0 AWG
Round-trip length
4 m
Fuse target at 125% load
150 A
Copper or aluminum area
53.48 mm²
Calculated drop
0.18 V · 0.35%
Cable loss
21.49 W
Adjusted ampacity
150 A
Cable drop against the voltage budget
Drop budget 1.024 V Screened wire drop 0.179 V
Neighboring gauges
AWGmm²Ω/kmAmpacityDropScreen
233.630.593115 A0.56%Outside limits
142.410.47130 A0.44%Outside limits
1/053.480.373150 A0.35%Pass
2/067.430.296175 A0.28%Pass
3/085.030.235200 A0.22%Pass
Main fuse candidates
TypeCurrent candidateExample DC ceiling
Class T150 A125 V
ANLNo fit in reference range32 V
MRBFNo fit in reference range58 V

Fuse candidates account for the entered 58.4 V circuit maximum. Check available fault current, interrupt rating, terminals and applicable installation rules.

Estimate DC current before choosing cable and protection

A 5,000 W inverter at 88% efficiency draws about 118 A at 48 V under steady load. This example rounds to 120 A and uses a 2 m one-way run with a 2% drop limit. The 51.2 V nominal value sets the drop budget. Recalculate current at the lowest expected inverter-terminal voltage and check its surge profile separately.

The tool screens the round-trip copper resistance, terminal temperature, reference ampacity and fuse voltage. Check the inverter manual for its cable and protective-device requirements. A final fuse and holder also need suitable DC voltage, interrupt rating, time-current behavior and conductor protection for the installation.

Formulas

  • DC load current = AC output watts ÷ (loaded DC volts × inverter efficiency)
  • Cable drop = DC amps × resistance of outgoing and return cables
  • Reference fuse screening current = 1.25 × continuous DC load amps

Worked example

At 120 A with a 2 m one-way run, the loop is 4 m and the 2% voltage budget is 1.024 V. The example 75 °C terminal and copper raceway settings return 1/0 AWG and a 150 A Class T screening candidate.

Engineering references

Frequently asked questions

How many DC amps does a 48 V 5,000 W inverter draw?

At 48 V under load and 88% conversion efficiency it draws about 118 A at full output. Lower loaded voltage or efficiency raises the current.

Which battery voltage belongs in the fuse screen?

Use the maximum circuit voltage, including the highest permitted charging voltage. This 16S example uses 58.4 V for that field.

Can I use the calculator’s fuse candidate for any 5 kW inverter?

Use the candidate as a starting point. Verify the inverter specification, cable and termination limits, surge tolerance, maximum voltage and available fault current.