Estimate DC current before choosing cable and protection
A 5,000 W inverter at 88% efficiency draws about 118 A at 48 V under steady load. This example rounds to 120 A and uses a 2 m one-way run with a 2% drop limit. The 51.2 V nominal value sets the drop budget. Recalculate current at the lowest expected inverter-terminal voltage and check its surge profile separately.
The tool screens the round-trip copper resistance, terminal temperature, reference ampacity and fuse voltage. Check the inverter manual for its cable and protective-device requirements. A final fuse and holder also need suitable DC voltage, interrupt rating, time-current behavior and conductor protection for the installation.
Formulas
DC load current = AC output watts ÷ (loaded DC volts × inverter efficiency)Cable drop = DC amps × resistance of outgoing and return cablesReference fuse screening current = 1.25 × continuous DC load amps
Worked example
At 120 A with a 2 m one-way run, the loop is 4 m and the 2% voltage budget is 1.024 V. The example 75 °C terminal and copper raceway settings return 1/0 AWG and a 150 A Class T screening candidate.