Off-Grid RV LiFePO4 Battery Bank Sizing Calculator

Size a 12.8 V or 25.6 V LiFePO4 bank for two off-grid days using a worked RV appliance list and an inverter surge check.

Jump to results

Inputs

Daily appliances
Appliance 1
Appliance 2
Appliance 3
Appliance 4
Appliance 5
Battery and inverter
Use the discharge curve for your cell and load.
Use the lower cell or BMS limit for the surge duration.

Results

Estimates
Minimum nominal bank3.05 kWh
Daily AC load
1,165 Wh
Required usable AC energy
2.33 kWh
Minimum nominal capacity
237.9 Ah
Estimated surge current
130.2 A
Surge at energy-only capacity
0.55 C
Nominal energy budget
AC load · 2.33 kWhInverter loss · 0.26 kWhDoD reserve · 0.46 kWhCold reserve · 0 kWh
  • AC load2.33 kWh
  • Inverter loss0.26 kWh
  • DoD reserve0.46 kWh
  • Cold reserve0 kWh
Parallel group options
Unit AhGroupsEnergy onlyInstalled AhRequired surge C
100333000.43
200224000.33
280112800.47
314113140.41

Group count covers both energy and the entered 1C surge limit. Verify BMS and inverter surge duration at the lowest operating voltage.

Build a two-day load budget for an RV or camper van

The worked example covers a portable fridge, cabin lighting, a laptop, a fan and a coffee maker, all on the AC side of the inverter. The fridge row uses equivalent compressor-on hours. Replace them with measured daily watt-hours when available and include any inverter standby draw in the budget.

Use two days to model a stop with no usable recharge. A 25.6 V bank needs about half the amp-hours and offers roughly half the surge current for the same nominal energy, subject to the voltage ratings of your inverter, charger and DC loads.

Formulas

  • Daily AC Wh = sum of watts × hours/day for each appliance
  • Required nominal Wh = daily Wh × autonomy days ÷ (inverter efficiency × DoD × cold capacity fraction)
  • Minimum Ah = required nominal Wh ÷ nominal bank volts

Worked example

The preset totals 1,165 Wh per day. Two days at 90% inverter efficiency and 85% DoD need about 3.05 kWh nominal, or about 238 Ah at 12.8 V and 119 Ah at 25.6 V. Verify the 1,500 W surge against the actual bank and inverter.

Frequently asked questions

How many Ah does the two-day RV example need at 12.8 V?

The energy budget requires approximately 238 Ah nominal at 12.8 V before choosing available modules. The surge rate can increase the number of parallel groups.

Can I use this calculator for direct DC van loads?

For an all-DC budget, use battery-side watts and set efficiency to 100%. For mixed systems, calculate the battery-side energy of the AC and DC loads separately and check AC inverter surge independently.

How do I account for cold weather on a winter trip?

Use a retained capacity measurement or the battery maker’s curves for the expected temperature and discharge rate. Check the allowed battery charging temperature separately.