Match solar string voltage to your MPPT
Start with daily load energy and the peak sun hours for the season you are designing around. A performance ratio accounts for aggregate losses. The city shortcuts are illustrative starting points. Adjust them for your site, month, tilt, shade and local design temperatures.
Evaluate both ends of the voltage window. Cold panels raise open-circuit voltage. Hot panels lower voltage at maximum power. The calculator reserves a percentage of the controller voltage rating and screens hot Vmp against full battery voltage plus 5 V. That start-up margin is a reference assumption. Use the controller’s operating and start-up limits for final design.
Each voltage class shows a possible string layout. Battery output amps and PV input short-circuit amps are separate ratings. The inverter estimate uses concurrent running loads plus 25% headroom and checks concurrent start-up power. Verify the required surge duration and apparent power for motors.
Formulas
Minimum PV watts = daily Wh ÷ (peak sun hours × performance ratio)Cold panel Voc = STC Voc × [1 + Voc coefficient × (cold temperature − 25 °C)]Estimated controller output A = installed PV watts ÷ nominal battery volts
Worked example
At −10 °C, a 41 V panel rated −0.30%/°C has an estimated Voc of 45.31 V. Two in series reach 90.61 V, which exceeds a 90 V design target on a 100 V controller with a 10% reserve.