DC Wire Gauge (AWG / mm²) & Voltage Drop Calculator

Check copper or aluminum DC wire against round-trip voltage drop, installation ampacity and fuse sizing.

Jump to results

Inputs

Circuit and voltage drop
Use full charge voltage when screening DC fuses.
Cable and installation
Enter the combined ambient and bundling adjustment.

Results

Estimates
Minimum reference gauge4 AWG
Round-trip length
9.14 m
Fuse target at 125% load
50 A
Copper or aluminum area
21.15 mm²
Calculated drop
0.35 V · 2.88%
Cable loss
13.8 W
Adjusted ampacity
85 A
Neighboring gauges
AWGmm²Ω/kmAmpacityDropScreen
88.372.38550 A7.27%Outside limits
613.31.565 A4.57%Outside limits
421.150.94385 A2.88%Pass
326.670.748100 A2.28%Pass
233.630.593115 A1.81%Pass
Main fuse candidates
TypeCurrent candidateExample DC ceiling
Class TNo fit in reference range125 V
ANL50 A32 V
MRBF50 A58 V

Fuse candidates account for the entered 14.6 V circuit maximum. Check available fault current, interrupt rating, terminals and applicable installation rules.

DC cable sizing checks voltage drop and heat

Measure the one-way cable run from source to load. The calculator doubles it for equal positive and return conductors. It estimates the DC resistance from nominal AWG area, bulk metal resistivity at 20 °C and the conductor temperature you enter. Stranding, terminals and actual cable construction can increase resistance.

The raceway reference assumes up to three loaded conductors and 30 °C ambient. The marine option uses the bundled copper column. Blank ampacity values indicate the selected table has no entry for that gauge. The lower of the insulation and terminal ratings sets the column. The raceway table stops at 90 °C, even when wire insulation says 105 °C.

The planning screen requires adjusted ampacity and applicable small-wire fuse caps to accommodate 125% of load. Check conductor, terminal and holder limits, time-current coordination, equipment marking and DC interrupt rating against the prospective battery fault current.

Formulas

  • Loop resistance = 2 × one-way distance × conductor resistance per meter
  • Voltage drop = load amps × loop resistance
  • Cable heat loss = load amps² × loop resistance

Worked example

A 10 A load on a 3 m one-way run uses 6 m of conductor resistance. With 2.08 Ω/km wire resistance, the loop drops about 0.125 V and dissipates about 1.25 W.

Engineering references

Frequently asked questions

Does one-way length include the negative wire?

Enter the distance in one direction. The calculator doubles it for equal outgoing and return conductors. Use the actual loop resistance if the paths use different lengths or materials.

Can 105 °C cable carry the 105 °C table current?

Only if the selected reference, terminal ratings, ambient and installation support it. Bundling reduces heat dissipation, and a 75 °C terminal may govern even with 105 °C insulation.

Is a fuse rating the same as its interrupt rating?

The ampere rating describes the protected operating current. The interrupt rating describes the prospective fault current the fuse can safely clear at a specified voltage. Check both the fuse and its holder.