DC cable sizing checks voltage drop and heat
Measure the one-way cable run from source to load. The calculator doubles it for equal positive and return conductors. It estimates the DC resistance from nominal AWG area, bulk metal resistivity at 20 °C and the conductor temperature you enter. Stranding, terminals and actual cable construction can increase resistance.
The raceway reference assumes up to three loaded conductors and 30 °C ambient. The marine option uses the bundled copper column. Blank ampacity values indicate the selected table has no entry for that gauge. The lower of the insulation and terminal ratings sets the column. The raceway table stops at 90 °C, even when wire insulation says 105 °C.
The planning screen requires adjusted ampacity and applicable small-wire fuse caps to accommodate 125% of load. Check conductor, terminal and holder limits, time-current coordination, equipment marking and DC interrupt rating against the prospective battery fault current.
Formulas
Loop resistance = 2 × one-way distance × conductor resistance per meterVoltage drop = load amps × loop resistanceCable heat loss = load amps² × loop resistance
Worked example
A 10 A load on a 3 m one-way run uses 6 m of conductor resistance. With 2.08 Ω/km wire resistance, the loop drops about 0.125 V and dissipates about 1.25 W.