LiFePO4 Battery Bank Sizing Calculator

Build a daily appliance budget, then size your LiFePO4 battery bank for backup days, cold weather and inverter surge.

Jump to results

Inputs

Daily appliances
Appliance 1
Appliance 2
Appliance 3
Appliance 4
Battery and inverter
Use the discharge curve for your cell and load.
Use the lower cell or BMS limit for the surge duration.

Results

Estimates
Minimum nominal bank2.54 kWh
Daily AC load
970 Wh
Required usable AC energy
1.94 kWh
Minimum nominal capacity
198.1 Ah
Estimated surge current
104.2 A
Surge at energy-only capacity
0.53 C
Nominal energy budget
AC load · 1.94 kWhInverter loss · 0.22 kWhDoD reserve · 0.38 kWhCold reserve · 0 kWh
  • AC load1.94 kWh
  • Inverter loss0.22 kWh
  • DoD reserve0.38 kWh
  • Cold reserve0 kWh
Parallel group options
Unit AhGroupsEnergy onlyInstalled AhRequired surge C
100222000.52
200112000.52
280112800.37
314113140.33

Group count covers both energy and the entered 1C surge limit. Verify BMS and inverter surge duration at the lowest operating voltage.

How to size a LiFePO4 battery bank

List each appliance once and multiply its measured watts by its daily run time. For cycling loads such as refrigerators, enter the equivalent hours at running power or measure a full day in watt-hours. The model treats all entries as inverter-fed AC loads. Set inverter efficiency to 100% for an all-DC budget.

The energy calculation first covers the load for all backup days, then allows for inverter losses, the chosen depth of discharge and reduced cold capacity. The peak power check is separate. A coffee maker might use little daily energy but draw more current than several smaller loads combined.

Formulas

  • Daily Wh = Σ(appliance watts × hours per day)
  • Nominal battery Wh = daily Wh × days ÷ (inverter efficiency × DoD × cold retained capacity)
  • Parallel groups = max(ceil(required Ah ÷ unit Ah), ceil(surge amps ÷ (unit Ah × surge C-rate)))

Worked example

A 1,000 Wh/day AC load for two days needs 2,000 Wh delivered. At 90% inverter efficiency and 80% DoD, the warm-weather bank needs 2,778 Wh, or 217 Ah at 12.8 V. Three 100 Ah parallel groups cover the energy requirement.

Engineering references

Frequently asked questions

How many Ah do I need for 1 kWh?

At 12.8 V, 1 kWh of nominal battery energy is 78.125 Ah. Usable energy at the load also depends on the allowed depth of discharge and inverter efficiency.

Should I choose 12 V, 24 V or 48 V?

For the same power, higher voltage reduces DC current. Choose a voltage supported by your inverter, charging equipment, fuses and loads. The nominal LFP equivalents are 12.8 V, 25.6 V and 51.2 V.

What cold battery capacity should I enter?

Use the manufacturer’s discharge curve at your expected temperature and current. The 25, 10 and 0 °C choices are editable planning examples. Check the charging temperature limit separately.