Series raises voltage. Parallel raises amp-hours.
This builder connects S stages in series. Each stage contains P identical units in parallel, so each stage sees the same series current and shares it among its units. The topology diagram shows those shared nodes. Pack mass and equivalent resistance cover the units only.
The BMS string count follows the series groups for bare cells. Its continuous current rating must meet the load, and its protection settings must respect the weakest cell, interconnect or thermal limit. A drop-in module has its own BMS. Use only the series and parallel arrangements the module manufacturer explicitly supports.
Formulas
Pack voltage = S × unit voltagePack Ah = P × unit AhPack Wh = pack voltage × pack AhEquivalent unit resistance = S × unit mΩ ÷ P
Worked example
A 16S1P pack using 3.2 V, 280 Ah LFP cells is rated at 51.2 V nominal and 14.336 kWh. A 3.65 V/cell upper limit gives 58.4 V. A second unit per stage doubles the nominal energy without changing the pack voltage.