Convert battery capacity into appliance run time
Amp-hours measure charge. Watt-hours measure energy at a given voltage. A LiFePO4 battery marked 100 Ah stores about 1,280 Wh at 12.8 V or 5,120 Wh at 51.2 V. Use nominal voltage for nameplate comparisons and measured power for load estimates.
The runtime simulator keeps the converter inputs independent so you can compare units without changing the scenario. It divides AC load by inverter efficiency, then adds DC standby draw. Enter efficiency at your expected load and standby only if it is separate from that efficiency figure.
Formulas
Wh = Ah × VkWh = Wh ÷ 1,000Runtime hours = available DC Wh ÷ (AC load W ÷ inverter efficiency + standby W)
Worked example
A 12.8 V, 100 Ah battery at 85% DoD provides 1,088 Wh. A 60 W AC load at 90% efficiency plus 8 W standby draws about 74.7 W from the battery for roughly 14 h 34 min.