Size a 25.6 V feeder from current and cable length
A 200 Ah battery describes stored charge. The wires carry the current demanded by the downstream loads. This example uses 60 A, equivalent to about 1.54 kW DC at 25.6 V nominal, with a 5 m one-way copper run.
The reference screen uses the full current path of 10 m and starts with a 3% drop budget. An enclosed, bundled or hot route can change ampacity. Use the battery and BMS current limits when checking the actual load and fault protection.
Formulas
Nominal LFP bank voltage = 8 × 3.2 VDrop budget in volts = nominal volts × drop fractionDrop (%) = 100 × load current × loop resistance ÷ nominal volts
Worked example
At 25.6 V, a 3% drop allows 0.768 V. The preset returns 4 AWG copper with about 0.57 V drop for a 10 m loop at 60 A. The terminal limit and fuse screening current also affect this result.